4/28
Software setup
Modicon TSX Micro
automation platform 0
Master modules for AS-Interface bus
The AS-Interface bus is configured using PL7 Micro/Junior/Pro software. The
services offered are based on the principle of simplicity:
b Management of profile tables, parameters and data by the master (this
management is transparent to the user).
b Topological I/O addressing: each AS-Interface slave declared on the bus is
assigned a topological address on the bus. This is transparent to the user.
b Each sensor/actuator for the AS-Interface bus interfaces is treated as an in-rack
I/O by the TSX Micro/Premium PLC.
All devices on the AS-Interface bus are configured implicitly using the following
sequence of screens:
b Declaration of the AS-Interface bus master module
v The TSX SAZ 10 module is always inserted and declared
in position no. 4 on
TSX 37 10/21/22 TSX Micro automation platforms.
v TSX SAY 100/1000 modules can be inserted into any position on
TSX/PCX 57 Premium
automation platforms (except positions reserved for
processors and power supplies).
b Configuration of AS-Interface slave devices
Using the configuration screen, it is possible to configure all the slave devices
corresponding to all interface I/Os on the AS-Interface bus. Depending on its type,
the configuration for each device consists of defining, as appropriate:
v Schneider Electric AS-Interface devices.
The user selects the AS-Interface device catalog reference from the various discrete,
analog, or safety interfaces listed. This selection
automatically determines the
AS-Interface profile and the parameters
associated with each interface.
v Third-party AS-Interface device.
The user can use PL7 Micro/Junior software to manage a “customized” list of
sensors/actuators of different brands. This list, specifying the AS-Interface profile
and parameters, is compiled to meet the needs of the user.
After configuration, the I/Os connected on the AS-Interface bus are processed by the
application program in the same way as an in-rack I/O of the PLC, using either the
address (e.g. %I\4.0\16.2, input 2 of slave 16 of the AS-Interface bus), or the
associated symbol (e.g. Start_conveyor).
PL7 Junior/Pro software has an integrated function block library containing the
specific diagnostic DFBs for AS-Interface bus. Its check for the appearance of any
error on the AS-Interface (bus or slaves).
Software setup
AS-Interface bus configuration
Programming
eclaration of the TSX SAZ 10 TSX Micro module
onfiguration of slave devices for TSX SAY 100
onfiguration of slave devices in TSX SAY 1000
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
efesotomasyon - telemecanique inverter